SYSTXCCITW01 &
SYSTXCCITN01
Infinityr Touch Control
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
US Patents: Carrierr U.S. Pat No. 7,243,004, Carrierr U.S. Pat No. 7,775,452,
pointSETt U.S. Pat No. 7,415,102
Seitenansicht 0
1 2 3 4 5 6 ... 83 84

Inhaltsverzeichnis

Seite 1 - Installation Instructions

SYSTXCCITW01 &SYSTXCCITN01Infinityr Touch ControlInstallation InstructionsNOTE: Read the entire instruction manual before starting the installatio

Seite 2

2conditions, and other data are passed continually between components over theABCD bus. The result is a new level of comfort, versatility, and simplic

Seite 3 - TABLE OF CONTENTS

3d If you make a mistake you may touch CANCEL and begin again.A121753.2. Set Dealer InformationFrom the main screen, touch MENU, on the bottom of the

Seite 4 - TABLE OF CONTENTS (cont.)

4S More detailed information can be found on HVACPartners.com under theProduct tab> Thermostats & Controls> SYSTXCCITW01> Documents &

Seite 5

54.3. LocationELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personal injuryor death.Disconnect power before routing contro

Seite 6

6S Close to or in direct airflow from supply registers.S In areas with poor air circulation, such as behind a door or in an alcove.4.3.2. Remote Room

Seite 7

7Sensor 1 Sensor 2Sensor 3 Sensor 4Damper ControlModuleZS_Damper ControlModuleZS_CA032334.3.3. Smart Sensors (for zoning applications)Any zone may use

Seite 8

8NOTE: ABCD bus wiring only requires a four--wire connection; however, it isgood practice to run thermostat cable having more than four wires in the e

Seite 9 - 2. Introduction

9ELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personal injuryor death.Before installing, modifying, or servicing system,

Seite 10 - 3.1. Set Time and Date

10S Adjust length and routing of each wire to reach each wire entry on theconnector backplate. Strip 1/4--in (6.4 mm) of insulation from each wire.S M

Seite 11 - 3.2. Set Dealer Information

114.4.2. Damper Control Module (zoning systems only)All wiring is run back to the Damper Control Module. Select a location near thefurnace or fan coil

Seite 13 - 4.3.1. Wall Control

12A12214A12215NOTE: Once Infinity Control is secured to wall with the backplate assembly(snapped together), care must be taken not to bend or break th

Seite 14 - 4.3.2. Remote Room Sensors

13A12213NOTE: Once the Infinity Touch Control is secured to wall with the backplateassembly (snapped together), care must be taken not to bend or brea

Seite 15 - 4.4. Wiring Considerations

14automatically energize the HUM output during a call for humidification. The N.O.relay contacts will be used to energize the humidifier . See fan pow

Seite 16

15A121785.2. Searching for Outdoor UnitThe Infinity Touch Control will then proceed to communicate with the outdoor unitby displaying “Searching for o

Seite 17

16A131185.3. Indoor Evaporator SelectionIf a furnace is installed with a variable capacity heat pump, a screen will appear toselect the installed indo

Seite 18 - 4.4.1. Shielded Wire

17A131195.4.1. Hydronic Heat ApplicationThe Infinity Touch Control supports 2 types of Hydronic Heat applications:1. Hot water coil in combination wit

Seite 19 - 4.5. Mounting

18A131175.5. Searching for SAM Module (If Applicable)“Searching for SAM Module” will appear on the screen to determine if a SystemAccess Module, used

Seite 20 - 4.5.1. Decorati ve Backplate

19A121855.7. Filter Type SelectionThe installer will next be prompted to select the air filter type installed with theInfinity System. After the selec

Seite 21 - 4.6.1. Bypass Humidifie r

20selected. If an incorrect selection was made, touch RE--INSTALL to restart theinstallation process.Example: SPP Equipment Summary ScreenA131205.11.

Seite 22 - 5. Commissioning

21approximately one minute p er zone. The duct assessment will override a call forheat or cool.A duct assessment will automatically occur each day at

Seite 23

TABLE OF CONTENTSPAGE1.Safety Considerations 1...2.Introduction 1...

Seite 24

226. Service MenuThe Service menus contain a set of vital information. This information enables theinstaller or service person to view a summary of wh

Seite 25

23Example: SPP Equipment Summary ScreenA131216.2. InstallationTouch INSTALLATION to perform the start--up process in order to learn allequipment in sy

Seite 26

24NOTE: For Small Packaged Products (SPP), please use the following instructionsfor Set --up (Section 6.3), Checkout (Section 6.4), and Service (Secti

Seite 27 - 5.10. Equipment Summary

25S Outdoor:d AC/Heat pumpd PAC AC outdoord PAC HP outdoord GAS PAC outdoord GAS PHP outdoorOnce the equipment has been selected, the appropriate menu

Seite 28 - 5.11. Static Pressure Check

266.3.1.2. Heat/Cool DeadbandThe minimum difference enforced between heating and cooling desiredtemperatures. This can allow one setting to “push” the

Seite 29

27d Default = On6.3.1.6. Smart Recovery EnableApplies to programmable operation only. Will start recovery 90 minutes prior toschedule change in both h

Seite 30 - 6.1. Equipment Summary

286.3.2.1. AirflowThis option allows the installer to select the appropriate air flow based on the needsof the installation. The QUIET airflow means t

Seite 31 - 6.2. Installation

296.3.2.3. Fan Coil DehumidificationThe Dehum Drain Time option turns off the continuous fan at the end of cooling forfive minutes in order to drain t

Seite 32 - 6.3. Set up

30d Normally Ope nd Normally Closed6.3.3. FurnaceFirst touch SETUP, then touch FURNACE to se t up the parameters for the furnaceunit.A121896.3.3.1. Fu

Seite 33 - 6.3.1.1. Auto Mode set up

316.3.3.2. AC/HP Air FlowThis option elects the airflow of the furnace when cooling, heat pump heating, anddehumidification.The QUIET airflow means th

Seite 34 - 6.3.1.5. Scheduling Enable

TABLE OF CONTENTS (cont.)PAGE4.6.1. Bypass Humidifier 13...4.6.2. Fan Powered Humidifiers 13...

Seite 35 - 6.3.2. Fan Coil

326.3.3.3. Furnace StagingThis option controls the staging of the furnace and selects the minimum amount oftime low stage must operate before high sta

Seite 36 - 6.3.2.2. Altitude

33d Default = 120 seconds6.3.3.6. AltitudeFor gas de--rating, this setting will adjust the furnace’s airflow to compensate foraltitude. Altitude adjus

Seite 37 - 6.3.2.4. Fan Coil G--Terminal

34S Fan Speed:Low,Med,orHighd Default = LowS Shutdown:d Normally Ope nd Normally Closed\d The shutdown function may not be immediate. Blower off delay

Seite 38 - 6.3.3.1. Furnace Airflow

35A121906.3.4.1. Cooling LockoutOutside temperature below which cooling will not be provided. After the selectionis made, touch SAVE.S Cooling Lockout

Seite 39 - 6.3.3.2. AC/HP Air Flow

36d Default = 30 minutes6.3.4.3. Low Ambient CoolingSelecting YES will enable the low ambient cooling operation in the outdoor unit.This setting is on

Seite 40 - 6.3.3.5. Furnace Off Delay

37switching reversing valve. This setup is only available on communicating heatpumps. After the selection is made, touch SAVE.S Defrost Fan Delay: Yes

Seite 41 - 6.3.3.8. Furnace G Terminal

38A12149S HP Lockout: Adjustable from 5 to 55_F(--15to13_C) or Noned Default = NoneS Furnace, Electric Heat o r Hydronic Lockout: Adjustable from 5 to

Seite 42 - 6.3.4. AC/Heat Pump

39A121916.3.6.1. Zoning DisableThis option allows the installer to enable or disable zoning. After the selection ismade, touch SAVE.S Disable Zoning:

Seite 43 - 6.3.4.2. Defrost Interval

40airflow; HIGH means 250% of maximum assessed airflow; and NO LIMIT meansthe equipment does not stage down.CFM associated for each limit is shown on

Seite 44 - 6.3.4.6. Defrost Fan Delay

41A121926.3.7.1. FilterWith this option, the installer has the option of selecting pressure monitoring, thetype of filter installed, and the time inte

Seite 45 - 6.3.5. Heat Source Lockout

TABLE OF CONTENTS (cont.)PAGE6.3.1. Thermostat 25...6.3.1.1.Auto Mode set up 25...

Seite 46 - 6.3.6. Zoning (If Applicable)

42S Change Pad: Selectable from 1 to 24 monthsd Default = 12 monthsS Humidify with Fan: Yes or Nod Default = No6.3.7.3. Ultraviolet LightsWith this op

Seite 47 - 6.3.6.3. Zone Airflow Limits

43lows stage when the curtailment function is active. After the selections are made,touch SAVE.A12193S Cooling: Disabled, Low Stage or Turn offd Defau

Seite 48 - 6.3.7. Accessories

44S Airflow: Selectable between Off to Max in 50 CFM incrementsd Off = 450 CFM, MAX = (odu_size in KBTU * 400) / 12)d Default = OffS Blower On Delay:

Seite 49 - 6.3.7.2. Humidifier

45S Medium Heat: Selectable from 0 to 120 minutesd Default = 5 minutesS High Heat: Selectable from 0 to 120 minutesd Default = 5 minutes6.4.2. Furnace

Seite 50 - 6.3.8. Utility Curtailment

46display will change to show the AC operating status. After the selections are made,touch START.NOTE: Airflows during Checkout modes are fixed to the

Seite 51 - 6.3.9. Hydronic Airflow

47100%d Default = lowest available as specified by variable speed heat pumpS Defrost: Yes or Nod Default = No6.4.6. Heat Pump CoolingThe heat pump coo

Seite 52 - 6.4.1. Electric Heat

486.4.8. VentilatorThe ventilator can be exercised through all of its operating speeds with this menuoption. T o end the ventilator checkout, touch ST

Seite 53 - 6.4.4. Air Conditioning

49After proper damper operation has been verified, the installer can now check andverify that each Remote Room Sensor corresponds to the proper zone d

Seite 54 - 6.4.5. Heat Pump Heating

50A131236.5.1. Fan Coil StatusThe fan coil status screen displays relevant information about the fan coil operation.To return to the previous screen,

Seite 55 - 6.4.7. Humidifier

51A121986.5.3. AC StatusThe AC status screen displays relevant information about the AC operation. Toreturn to the previous screen, touch BACK. To exi

Seite 56 - 6.4.9.2. Damper/Sensor Check

TABLE OF CONTENTS (cont.)PAGE6.3.3.7.Furnace Dehumidifier Drain 33...6.3.3.8.Furnace G Terminal 33...

Seite 57 - 6.5. Service Information

52A122006.5.5. Zoning StatusThe zoning status screen displays relevant information about the zoning operation.To return to the previous screen, touch

Seite 58 - 6.5.2. Furnace Status

53equipment that generated the event. To return to the previous screen, touch BACK.To exit the Service menus, touch DONE.A121516.5.7. Run/Fault Histor

Seite 59 - 6.5.4. Heat Pump Status

54A122026.5.8. Model/Serial NumbersThis menu item allows the installer to view the model number and serial number (ifavailable) of all communicating p

Seite 60 - 6.5.6. Last 10 System Faults

55A122036.6. Refrige rant ChargingFor variable speed heat pumps, a refrigerant charging menu is available to aid in theproper charging of the system.

Seite 61 - 6.5.7. Run/Fault History

56S Vapor line: Selectable with various diameters by using the up and downbuttonsNext, the installer will enter the WEIGH IN screen to verify the curr

Seite 62 - 6.5.9. Service Phone Number

576.6.3. EvacuationBecause this system has an EXV for the heating expansion device, additional stepsmust be taken to open the EXV if the heat pump uni

Seite 63 - 6.6.1. Charging

58The PC/MAC software application to format the dealer logo and contactinformation can be found at:www.MyInfinityTouch.Carrier.com/Infinity/downloadsD

Seite 64 - 6.6.2. Pump down

59(LAN). An Infinityr Wireless Access Point is provided in the Infinity TouchControl Wi-- Fi bundle to ease connection of the Infinityr System to a ho

Seite 65 - 6.7. Dealer Logo

60(BLUE port) of the TP--LINKr Wireless Access Point (supplied with the InfinityTouch Control Wi--Fi Bundle) to an open LAN port on the homeowner’s ex

Seite 66

61A12206S Verify that the Wi -- Fi connection is enabled, by noting that ENABLED ishighlighted in green.S Touch SETUP A WI--FI CONNECTION to begin the

Seite 67

TABLE OF CONTENTS (cont.)PAGE6.3.7. Accessories 40...6.3.7.1.Filter 41...

Seite 68

62d You may have to use the down arrow to scan to the next screen to find the“myHVACxxxxxx”SSIDA12162S Use the on-- screen keyboard to enter the Wi--

Seite 69

63d If the connection is unsuccessful, verify the Wireless Access Point SSIDand Security Key from the label on the bottom of the Wireless AccessPoint.

Seite 70

64Once Internet connectivity is established, the weather forecast should appear on theHOME screen and on the WEATHER button/screen, found on the secon

Seite 71

658. Appendix A -- Wiring DiagramsABCDABCDUser InterfaceGreen - Data AYellow - Data BWhite - COMRed - 24VACOATOptional RemoteRoom SensorHUMCOM24VHumid

Seite 72

66ABCDABCDCYABCDConnectionUser Interface 1-Spd.Non-Communicating AC Green - Data AYellow - Data BWhite - COMRed - 24VACOptional

Seite 73 - Furnace/ Fan Coil

67ABCDABCDABCDConnectionUser Interface 1-Spd.Non-communicating HPGreen - Data AYellow - Data BWhite - COMRed - 24VACOptional

Seite 74 - Furnace/Fan Coil

68ABCDZone ControlUser Interface &Smart Sensor(s)GreenYellowWhiteRedOATHUMCOM24VHumidifierConnectionABCD OATSensor(Optional)A B C D A B C DDamperC

Seite 75 - Fan Coil

69ABCDZone ControlUser Interface &Smart Sensor(s)GreenYellowWhiteRedOATHUMCOM24VHumidifierConnectionOATSensorA B C D A B C DDamperControlmoduleA B

Seite 76 - (Optional)

70ABCDZone ControlUser Interface &Smart Sensor(s)GreenYellowWhiteRedA B C D A B C DDamperControlmoduleA B C DVariable-SpeedFan Coil1-Spd. HPHUMCYW

Seite 77 - 1-Stage AC

71RGFE Fan Coil or Variable Speed FurnaceA07114G Input Wiring for Blower Operation

Seite 78 - 1-Spd. HP

TABLE OF CONTENTS (cont.)PAGE6.4.9.3.Zone Duct Assessment 49...6.4.9.4.Sensor Type 49...

Seite 79 - Variable Speed Furnace

72RGFE Fan Coil or Variable Speed FurnaceA07115G Input Wiring for System Shutdown

Seite 80

73NOTES:

Seite 81

74NOTES:

Seite 83

Infinity and HYBRIDHEAT are trade marks or registered tra demarks of CarrierCorporation in the United States and other countries. Other brands and pro

Seite 84 - Catalog No: SYSTXCCITW---06SI

11. Safety ConsiderationsImproper installation, adjustment, alteration, service, maintenance, or use can causeexplosion, fire, electrical shock, or ot