Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
1014. See Table 4 for normal operating ranges. Check thesecharacteristics hourly, recording readings in refrigerationlog. Refrigeration log should inc
112. If the machine will be exposed to freezing temperatures,drain all water from cooler and condenser. Blow out oilcooler lines to remove all traces
124. Start the pumpout compressor (control switch at ONposition).5. Operate pumpout compressor until suction gage readshighest sustained vacuum (about
132. Open valves 1, 2, 5, 6, 7, and 12.3. Close valves 3, 4, 8, 9, 10 ,11, and 13. 4. Operate the pumpout compressor (control switch in theON position
14refrigerant side of the seal and the oil supply being controlledby the differential pressure regulator. The pressure being sup-plied to the seal is
15machine refrigerant pressure, so that any oil leakage throughthe seal is always in an inward direction.CHECK STARTERS AND VFDS — Refer to the sta
16BREAKING VACUUM — When breaking vacuum duringleak testing or other service work, always use dry refrigerant orother form of dry gas; i.e., nitrogen
17to the vacuum indicator only when taking a reading.Leave the valve open for 3 minutes to allow the indicatorvacuum to equalize with the chiller vacu
18• Controls - Instruments which control the brine temperature,protect the various elements of the machine, and automati-cally start and stop the comp
19Auxiliary oil pump, if used, operates when seal oil andback-of-seal oil pressure difference is less than 23 psi. Controlis located on machine safety
2CONTENTSPageSAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20During shutdown all pressures equalize and refrigerant willnot separate from air in the purge. Do not vent the purge whenthe machine is not running.
21Table 6A — HFC-134a Pressure —Temperature (F)Table 6B — HFC-134a Pressure —Temperature (C)TEMPERATURE,FPRESSURE(psig)0 6.502 7.524 8.606 9.668 10.79
22Chilled Water Temperature Too Low withCompressor RunningCHILLED WATER SET POINT IN THE PLC SET TOOLOW — Correct set point and check for overrides fr
23use the same sensors as the operating functions. Per customerspecifications, these may be supplemented by mechanicalswitches which directly measure
24Fig. 10 — Typical 17DA Motor-Driven Machine Control DiagramPLC — Programmable Logic Controllera17-579
25Fig. 11 — Typical 17DA Turbine-Driven Machine Control DiagramPLC — Programmable Logic Controller
26Fig. 12 — Machine ConfigurationFRONT VIEWREAR VIEW
27Fig. 12 — Machine Configuration (cont)COMPRESSOR FRONT VIEWCOMPRESSOR REAR VIEWLEGEND 1—Free Cooling Vapor Valve (optional)2—Sub-Cooler Refrigerant
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
3INTRODUCTIONGeneral — All persons concerned with the start-up and op-eration of the centrifugal refrigeration machine should be fa-miliar with the eq
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
4trip is a good example of the type of safety that acts directly. Ifspecified, there may be both sensor inputs and mechanicalswitches monitoring some
5Table 2 — Pumpout System RatingsCharge Machine with Water — When the machinehas been proved leak tight and dry, it may be filled with water,brine or
64. If realignment is required, follow instructions supplied bycoupling manufacturer. Carrier Standard Service Tech-niques, Form SM-15, Rev A, also de
7The proportional band can be adjusted on the PLC to sta-bilize the level if necessary.3. Start the compressor. Observe the machine's operation f
8Table 3B — Typical 17DA Cooler and Condenser Charges (R-134a) (Kg)4. Location of isolation transformer, incoming switch gear.5. Operation and servici
9REFRIGERATION LOG CARRIER 17DA CENTRIFUGAL REFRIGERATION MACHINEPlant MACHINE MODEL NO. MACHINE SERIAL NO. REFRIGERANT TYPE REMARKS: Indicate shut
Kommentare zu diesen Handbüchern