Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48EJ Spezifikationen

Stöbern Sie online oder laden Sie Spezifikationen nach Wärmepumpen Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48EJ herunter. Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48EJ Specifications Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 64
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INSTALLATION .............................1-31
Step 1 Provide Unit Support ...............1
ROOF CURB
ALTERNATE UNIT SUPPORT
Step 2 Rig and Place Unit ..................2
POSITIONING
ROOF MOUNT
Step 3 Field Fabricate Ductwork ............2
Step 4 Install Flue Hood ..................12
Step5—TrapCondensate Drain ............13
Step 6 Install Gas Piping ..................13
Step 7 Controls Options ..................13
CONSTANT VOLUME APPLICATIONS
VARIABLE AIR VOLUME (VAV) APPLICATIONS
Step 8 Make Electrical Connections .......16
POWER WIRING
FIELD POWER SUPPLY
FIELD CONTROL WIRING
Step 9 Make Outdoor-Air Inlet
Adjustments ...............................24
ECONOMIZER
ECONOMIZER SETTINGS
Step 10 Position Power Exhaust/Barometric
Relief Hood ...............................29
Step 11 Install All Accessories ............30
START-UP ................................31-44
SERVICE ..................................44-55
TROUBLESHOOTING ......................56-61
START-UP CHECKLIST ................CL-1,CL-2
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical com-
ponents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters.
All other operations should be performed by trained service
personnel. When working on air-conditioning equipment, ob-
serve precautions in the literature, tags and labels attached
to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire ex-
tinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
1. Improper installation, adjustment, alteration, serv-
ice, or maintenance can cause property damage, per-
sonal injury, or loss of life. Refer to the User’s
Information Manual provided with this unit for more
details.
2. Do not store or use gasoline or other flammable va-
pors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone
in your building.
3. IMMEDIATELY call your gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire
department.
Disconnect gas piping from unit when pressure testing
at pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in haz-
ardous condition. If gas valve is subjected to pressure
greater than 0.5 psig, it must be replaced before use. When
pressure testing field-supplied gas piping at pressures of
0.5 psig or less, a unit connected to such piping must be
isolated by closing the manual gas valve(s).
INSTALLATION
Step 1 Provide Unit Support
1. All panels must be in place when rigging.
2. Unit is not designed for handling by fork truck.
ROOF CURB Assemble or install accessory roof curb in
accordance with instructions shipped with this accessory. See
Fig. 1 and 2. Install insulation, cant strips, roofing, and counter
flashing as shown. Ductwork can be installed to roof curb
before unit is set in place. Curb should be level. This is nec-
essary to permit unit drain to function properly. Unit level-
ing tolerance is shown in Fig. 1 and 2. Refer to Accessory
Roof Curb Installation Instructions for additional informa-
tion as required. When accessory roof curb is used, unit may
be installed on class A, B, or C roof covering material.
IMPORTANT: The gasketing of the unit to the roof
curb is critical for a watertight seal. Install gasket with
the roof curb as shown in Fig. 1 and 2. Improperly
applied gasket can also result in air leaks and poor unit
performance.
48EJ,EK,EW,EY024-048
Single Package Rooftop Units
Electric Cooling/Gas Heating
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab 1a
PC 111 Catalog No. 564-962 Printed in U.S.A. Form 48E-5SI Pg 1 8-97 Replaces: 48E-3SI
Seitenansicht 0
1 2 3 4 5 6 ... 63 64

Inhaltsverzeichnis

Seite 1 - Service Instructions

Installation, Start-Up andService InstructionsCONTENTSPageSAFETY CONSIDERATIONS ...1INSTALLATION ...1-31Step

Seite 2

Table 1 — Physical DataUNIT 48EJ,EK,EW,EY 024D/E 028D/E 030D/E 034D/ENOMINAL CAPACITY (tons) 20 25 27 30OPERATING WEIGHT (lb)*UnitAl/Al† (Lo Heat/Hi H

Seite 3

Table 1 — Physical Data (cont)UNIT 48EJ,EK,EW,EY 038D/E 044D/E 048D/ENOMINAL CAPACITY (tons) 35 40 45OPERATING WEIGHT (lb)*UnitAl/Al† (Lo Heat/Hi Heat

Seite 4

Table 2 — Evaporator Fan Motor Data (Units with Starting Serial Numbers 4197 and Later)UNITSIZE48EMOTORHPMOTORSHAFTDIA.(in.)FANSHAFTSPEED(rpm)MOTORSHE

Seite 5

Step5—TrapCondensate Drain — See Fig. 3-6for drain location. Condensate drain is open to atmosphereand must be trapped. Install a trapped drain at the

Seite 6

Table 3 — Controls Options and Configurations (Non-Thermostat Applications)UNIT CONFIGURATION DEFAULT COOLING DEFAULT HEATINGCV or VAV Unit with SPT Se

Seite 7

Features with Sensor Control of Unit (Network Applica-tions) — The base control board provides, as standard, a con-nection for use with a Carrier VVT

Seite 8

When a VAV unit with a space temperature sensor is ac-cessed via a computer, the following additional features areavailable:• ability to initiate time

Seite 9

LEGENDCCN — Carrier Comfort NetworkCOM — CommonD—DiodeLED — Light-Emitting DiodeN.C. — Normally ClosedN.O. — Normally OpenR—RelaySIO — Serial Input/Ou

Seite 10 - Table 1 — Physical Data

Table 4 — Electrical DataUNITSIZE48ENOMNALVOLTAGE(3 Ph 60 Hz)VOLTAGERANGECOMPRESSOROFM IFMPOWEREXHAUSTCOMBUSTIONFAN MOTORPOWER SUPPLYNo. 1 No. 2Min Ma

Seite 11

Table 4 — Electrical Data (cont)UNITSIZE48ENOMINALVOLTAGE(3 Ph 60 Hz)VOLTAGERANGECOMPRESSOROFM IFMPOWEREXHAUSTCOMBUSTIONFAN MOTORPOWER SUPPLYNo. 1 No.

Seite 12

ALTERNATE UNIT SUPPORT — When the preferred curbor slab mount cannot be used, support unit with sleepers onperimeter, using unit curb support area. If

Seite 13

Table 4 — Electrical Data (cont)UNITSIZE48ENOMINALVOLTAGE(3 Ph 60 Hz)VOLTAGERANGECOMPRESSOROFM IFMPOWEREXHAUSTCOMBUSTIONFAN MOTORPOWER SUPPLYNo. 1 No.

Seite 14 - of 5° F

IMPORTANT: THE VAV (variable air volume) unitsuse variable frequency drives, which generate, use andcan radiate radio frequency energy. If units are n

Seite 15 - Field Supplied Wiring

LEGENDFig. 20 — Field Control Thermostat WiringNOTE: Sensor part numbers are as follows:T-55 — CEC0121448-01T-56 — CEC0121503-01Fig. 21 — Field Contro

Seite 16

Remote Field Control — A switch closure across terminalsR and W1 on TB-3 will initiate the Occupied mode. Thiscan be done manually as well as through

Seite 17

IMPORTANT: When connecting the CCN communi-cation bus to a system element, use a color coding sys-tem for the entire network to simplify installation

Seite 18 - Table 4 — Electrical Data

HOOD SIDETOPFLANGESEALSTRIPBLACKFig. 23 — Adding Seal Strip to Top of Hood SidesNOTE: Left side economizer hood has mounting angle without tabsand filt

Seite 19

The outdoor-air damper closes. The control allows 90 sec-onds for the damper to close in case it is in the full openposition. Next, the indoor-fan con

Seite 20

Differential Enthalpy Sensor Installation — To install the con-trol, perform the following procedure:1. Turn off all power. Ensure disconnect is locke

Seite 21 - TB — Terminal Block

NOTE: Switches shown in high enthalpy state. Terminals 2 and 3 closeon enthalpy decrease.Fig. 34 — Wiring Connections for Solid-StateEnthalpy Control

Seite 22 - (CV or VAV Units)

Step 10 — Position Power Exhaust/BarometricRelief Damper Hood —All electrical connections havebeen made and adjusted at the factory. The power exhaust

Seite 23

NOTES:1. All roof curb parts are to be 16 ga galvanized steel.2. Dimensions are in inches.3. To prevent standing water in the drain pan of the indoors

Seite 24

Step 11 — Install All Accessories — After all thefactory-installed options have been adjusted, install all field-installed accessories. Refer to the ac

Seite 25

START-UPUse the following information and Start-Up Checkliston page CL-1 to check out unit PRIOR to start-up.Unit Preparation — Check that unit has be

Seite 26 - ASSEMBLY

To set the VFD, the VFD must be powered up; however,since it is located near the indoor air fan, operation of thefan is not desirable. To disable the

Seite 27 - C7400A1004

At the upper right corner of the board is a set of 5 pins andjumper, which determines the time constant for the control.The time constant is the delay

Seite 28 - RH — Relative Humidity

Table 9 — Power Exhaust Default Set PointsSTAGE OFFSET DIFFERENTIAL OFF VOLTAGE ON VOLTAGEOFF STATIC PRESSURE(in. wg)1 50% 3% 6.0 6.3 0.002 55% 3% 6.5

Seite 29 - Relief Damper Hood —

Table 12 — Fan Performance, 48EJ/EK024-034 — Vertical Discharge Units(For EW/EY units, reduce net available external static pressure by 0.3 in. wg)AIR

Seite 30 - VAV — Variable Air Volume

Table 13 — Fan Performance, 48EJ,EK038,044 — Vertical Discharge Units(For EW/EY units, reduce net available external static pressure by 0.5 in. wg)AIR

Seite 31

Table 14 — Fan Performance, 48EJ,EK048 — Vertical Discharge Units(For EW/EY units, reduce net available external static pressure by 0.5 in. wg)AIRFLOW

Seite 32

Table 15 — Fan Performance — Power Exhaust48EJ,EK,EW,EY024-048 (20 THRU 45 TONS)Airflow(Cfm)Low Speed Medium Speed High Speed208 v 230, 460, 575 v 208

Seite 33

Table 17 — Air Quantity LimitsUNIT48EJ,EK,EW,EYMINIMUM HEATINGAIRFLOW(Low Heat)MINIMUM HEATINGAIRFLOW(High Heat)MINIMUM COOLINGAIRFLOW (VAV)AT FULL LO

Seite 34

NOTES:1. All roof curb parts are to be 16 ga galvanized steel.2. Dimensions are in inches.3. To prevent standing water in the drain pan of the indoors

Seite 35

Table 18 — User Defined Set PointsSET POINTNAMEFORMAT DESCRIPTION LIMITS DEFAULTOHSP xx.xF Occupied Heat Set Point 55 to 80 F 68 FOCSP xx.xF Occupied C

Seite 36

When cooling, the control will energize the power ex-haust enable output to the external power exhaust controller,when power exhaust is used.If occupi

Seite 37

MORNING WARM-UP (VAV Only) (Stand-Alone Opera-tion) — When the unit operates in stand-alone mode, morn-ing warm-up occurs when the unit is energized i

Seite 38 - Table 16 — Motor Limitations

Space Temperature Reset Example — The occupied coolingset point is set to 73 F. The Reset Ratio is set to 5. The ResetLimit is set to 20° F. The Reset

Seite 39 - input will be used

• When the outdoor air quality is greater than the outdoorair quality set point (ppm)High priority — When the priority is set to high, the IAQset poin

Seite 40

To open, loosen the latch bolt using a7⁄16-in. wrench. Pivotthe latch so it is not in contact with the door. Open the door.To shut, reverse the above

Seite 41

Evaporator Fan Performance Adjustment(Fig. 49) —Fan motor pulleys are designed for speed shownin Table 1 (factory speed setting).IMPORTANT: Check to e

Seite 42

Evaporator-Fan Motor Replacement1. Shut off unit power supply.2. Remove upper outside panel and open hinged door togain access to motor.3. Fully retra

Seite 43

Main Burners — For all applications, main burners arefactory set and should require no adjustment.MAIN BURNER REMOVAL (Fig. 55)1. Shut off (field-suppl

Seite 44

Crankcase Heater — Each compressor has a crankcase heaterto prevent absorption of liquid refrigerant by oil in the crank-case when the compressor is i

Seite 45 - Lubrication

VFD — Variable Frequency DriveNOTES:1. Weights include economizer (STD).2. Center of gravity.3. Do not locate adjacent units with flue dis-charge facin

Seite 46 - (Fig. 49) —

LEGEND and NOTES for Fig. 56-60 — Typical Wiring SchematicsAHA — Adjustable Heat AnticipatorBP — Building PressureBR — Burner RelayC—Contactor, Compre

Seite 47

Fig. 56 — Typical Power Schematic; 48EJ,EK,EW,EY024-034; 208/230-3-60 and 460-3-6051

Seite 48 - Protective Devices

Fig. 57 — Typical VAV 115-v Control Circuit52

Seite 49

Fig. 58 — Typical CV 115-v Control Circuit53

Seite 50

Fig. 59 — Typical VAV 24-v Control Circuit54

Seite 51

Fig. 60 — Typical CV 24-v Control Circuit55

Seite 52

TROUBLESHOOTINGTypical refrigerant circuiting diagrams are shown in Fig. 61-63. An algorithm diagram of the IGC (Integrated Gas Unit Con-troller) cont

Seite 53

LEGENDFPS — Freeze Protection SwitchHPS — High-Pressure SwitchLPS — Low-Pressure SwitchFig. 62 — Typical Refrigerant Circuiting (48EJ,EK,EW,EY038,044)

Seite 54

LEGENDFPS — Freeze Protection SwitchHPS — High-Pressure SwitchLPS — Low-Pressure SwitchFig. 63 — Typical Refrigerant Circuiting (48EJ,EK,EW,EY048)58

Seite 55

NOTE: Thermostat Fan Switch in the ‘‘AUTO’’ position or sensor-equipped unit.Fig. 64 — IGC Control (Heating and Cooling)LEGENDIDM — Induced-Draft Moto

Seite 56 - TROUBLESHOOTING

VFD — Variable Frequency DriveNOTES:1. Weights include economizer (STD).2. Center of gravity.3. Do not locate adjacent units with flue discharge facing

Seite 57 - LPS — Low-Pressure Switch

The alarm codes for the IGC control board are shown inTable 22.Table 22 — IGC Control Board LED AlarmsINDICATION ERROR MODEON Normal OperationOFF Hard

Seite 58

Tables 24-26 show the input and output channeldesignations.Table 24 — I/O Channel Designations Base Module — CVTERMINAL NO. ASSIGNMENT TERMINAL NO. AS

Seite 59 - IDM — Induced-Draft Motor

PACKAGED SERVICE TRAININGOur packaged service training programs provide an excellent way to increase your knowledge of theequipment discussed in this

Seite 60

START-UP CHECKLISTMODEL NO.:SOFTWARE VERSION (SEE FIG. 16)DATE:SERIAL NO.:TECHNICIAN:PRE-START-UP:M VERIFY THAT DIP SWITCH SETTINGS ARE CORRECTM VERIF

Seite 61 - T—Terminal

GENERALM SET ECONOMIZER MINIMUM VENT POSITION TO JOB REQUIREMENTSM ENSURE DRIVES OPERATE WITHIN LIMITS OF FAN PERFORMANCE TABLESHIGH PRESSURE SWITCH S

Seite 62 - PACKAGED SERVICE TRAINING

VFD — Variable Frequency DriveNOTES:1. Weights include economizer (STD).2. Center of gravity.3. Do not locate adjacent units with flue discharge facing

Seite 63 - START-UP CHECKLIST

VFD — Variable Frequency DriveNOTES:1. Weights include economizer (STD).2. Center of gravity.3. Do not locate adjacent units with flue discharge facing

Seite 64

UNITWEIGHT A B Clb kg in. mm in. mm in. mm48EJ,EK,EW,EYD024 4176 189487.68 222772.4 1839 42.4 107248EJ,EWE024 4256 1930 73.3 1862 42.7 108548EJ,EK,EW,

Kommentare zu diesen Handbüchern

Keine Kommentare