Installation, Start-Up '
and Service Instructions
Carrier Parkway • Syracuse NY 13221
Air-Cooled Condensing Units
Page
.. 1
. 1-6
INDEX
SAFETY CONSIDERATIONS......................
INSTALLATION
...........................................
Step 1 — Check Equipment and
Jobsite..............................................................I
UNPACK UNIT
INSPECT EQUIPMENT
COMPLETE OR CONSIDER
SYSTEM REQUIREMENTS
Step 2 — Make Piping Connections
_______
2
REPLACE THE ACCURATER™
REFRIGERANT CONTROL
PISTON IN THE INDOOR
COIL IF REQUIRED
CONNECT REFRIGERANT LINES
Step 3 — Make Electrical
Connections....................................................5
INSTALL A BRANCH CIRCUIT
DISCONNECT PER NEC
ROUTE LINE POWER LEADS INTO
UNIT
CONNECT GROUND LEAD AND
POWER WIRING
CONNECT CONTROL POWER
WIRING
START-UP
...........................................................
6-8
SERVICE............................................................. 8-10
MAINTENANCE..................................................11,12
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning
equipment can be hazardous due to system pressure
and electrical components. Only trained and quali
fied service personnel should install, repair or
service air conditioning equipment.
Untrained personnel can perform basic mainten
ance functions of cleaning coils and filters and re
placing filters. All other operations should be
performed by trained service personnel. When
working on air conditioning equipment, observe
precautions in the literature, tags and labels attached
to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing opera
tions. Have fire extinguisher available for all brazing
operations.
WAR-NiNG: Before perfosrmisg service or
majnteiiatice орегайоиз or system, tarn off
vaaia power to isdoor tmit tsml outdoor
■ask. Тош off accessory beater power switch is
appiicaMe, E^ecfircal sihock, could cause per-
s<mal injury.
Table 1 — Physical Data (Refer to Fig. 1)
MODEL38EB
015 018
024
030
036
042
048 060
OPER WT(lb)
116
130
137 165 181
212 230.
DIMENSIONS (ft-in.)
Diameter A
Height B
1-9-3/4
2-2-3/8 ) 2-8
2-5-1/4
2-2-3/8 1 2-8 1 3-2
CONNECTIONS (in.)
Suction (ODF)
Liquid (ODF)
5/8
3/
3/4*
8
REFRIG LINES
Suction (in. ODF)
Liquid (in ODF)
Recommended Field-Supplied Sizes
5/8 i 3/4 i 7/8 1 1-1/8
3/8
*Fora1-1/8in suction line on 38EB048,060, a 3/4-in x 1-1/8 in suction
valve connection adapter is available as an accessory See Table 3
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT Move to final location. Slide
from carton taking special care not to damage serv
ice valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installation:
Consult local building codes and National Elec
trical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping and service.
Maintain a minimum of 4 ft clearance from obstruc
tions above and 18 in. on sides of unit. Maintain a
distance of 24 in. between condensing units. Posi
tion so water from roof or eaves does not flow
directly on unit.
Install on a solid, level mounting pad. It is not
necessary to attach unit to pad but if desired or
required by local code, position tiedown bolts in
pad. Fasten unit to pad using 2 holes provided in unit
base. See Fig. 1.
© Carrier Corporation 1982
Form 38EB-3SI
Seitenansicht 0
1 2 3 4 5 6 ... 11 12

Inhaltsverzeichnis

Seite 1 - Air-Cooled Condensing Units

Number One AirCoxIitbning l\MereDivision of Carrier CorporatioInstallation, Start-Up ' and Service InstructionsCarrier Parkway • Syracuse NY 1322

Seite 2

Unit Controls and Safety DevicesHIGH-PRESSURE RELIEF VALVE is located in compressor. Relief valve opens if system operating pressure differ

Seite 3

MAINTENANCE-^LubricationCOMPRESSOR contains factory oil charge. Replace oil when lost. See Table 8 for oil recharge and refer to Carrier Stan

Seite 4 - Table 3 — Accessories

TROUBLESHOOTING GUIDESYMPTOM AND PROBABLE CAUSEPROBABLE REMEDYCOMPRESSOR SHUTS OFF. FAN OVERLOADOR HIGH-PRESSURE SWITCH CUT OUT, ORINTERNAL PRESSURE R

Seite 5 - Do »ot ana ia

4'-0" OVERHEAD SPACE REQUIRED FOR SERVICE AND AIRFLOWLIQUID VALVE SERVICE PORT CONDENSER AIRFLOWKW r-6''AIRFL0W ••••• AND SER

Seite 6 - CAUTION: To

adapter (Carrier Part No. 28VQ900011) or to correctly sized field-supplied adapter, then make Compatible Fitting connections.WARNING: iX> NOT

Seite 7 - Fig. 6 — 38EB Charging Chart

Table 3 — AccessoriesPART NO.DESCRIPTIONMODEL38EB38CQ900141HH01AD040HH93AZ040HH07AT170&HH07AT174HH93AZ176HH01AD042HH93AZ042HH01YA192HH93YZ19438GS9

Seite 8

Table 4 — Electrical DataCONDUNIT38EBOPERVOLTS*BRANCH CIRCUITV/PHCOMPRFANFLAMin Wire Sizet (AWG)MaxFtWiretMin Ground Wire SizetMax Fuse or HACR Type C

Seite 9 - \ \ £8í№mw Í

THERMOSTAT SUBBASE HH93AZ042 OR HH93AZ04038EBI-jTO IFM LINE VOLTAGE :}“\POWER SUPPLY“©nTRANSARRANGEMENT A-(COOLING ONLY)THERMOSTAT SUBBASEARRANGEMENT

Seite 10

Table 5 — Service DataUNITR-22 CHG‘CONDENSER38EB(lb)FAN RPM0153000183003 311100243000303105 3036310 7 5042360 6 30483106 110750483507 20603509 6‘Facto

Seite 11

3. Connect Chargemaster outlet port to unit suction valve service port.4. Crack valves on refrigerant drum and Charge- master to purge lines f

Seite 12

SUCTION LINE HOT GAS DISCHARGE LINE\ \ £8í№mw Í.CONDENSER COIL COMPRESSORDISCHARGE GRILLE (FAN MOTOR UNDERNEATH)"WIRE ACCESS OPENING TOP COV