AIR CONDITIONER (MULTI TYPE)Indoor UnitModel name:High Wall TypeMMK-AP0073H2ULMMK-AP0093H2ULMMK-AP0123H2ULMMK-AP0153H2ULMMK-AP0183H2ULMMK-AP0243H2ULIn
High Wall TypeInstallation Manual–9– 5 Drain Piping Work Piping and drain hose forming* Apply heat-insulation for both refrigerant pipe and drain hos
High Wall TypeInstallation Manual–10– ENRemove the drains capClip the drain cap by needle-nose pliers and pull out.Fix the drains cap1) Insert a 4 mm
High Wall TypeInstallation Manual–11– ▼ Bottom right or bottom left piping• After scribing slits of the front panel with a knife or a marking-off pin,
High Wall TypeInstallation Manual–12– EN6 Indoor Unit Fixing1. Pass the pipe through the hole in the wall, and hook the indoor unit on the installatio
High Wall TypeInstallation Manual–13– 8 Refrigerant Piping Refrigerant Piping1. Use copper pipe with 0.03” (0.8 mm) or more thickness. (In case pipe
High Wall TypeInstallation Manual–14– ENTightening connectionCAUTION• Do not apply excessive torque. Otherwise, the nut may crack depending on the con
High Wall TypeInstallation Manual–15– Wireless remote control A-B selectionTo use 2 wireless remote controls for the respective air conditioners, wh
High Wall TypeInstallation Manual–16– EN9 Electrical ConnectionWARNING1. Use predefined wire and connect them certainly. Keep the connecting terminal
High Wall TypeInstallation Manual–17– Power supply wire• Recommended wire diameter and wire length for power supply wire.Electric characteristicsContr
High Wall TypeInstallation Manual–18– EN Wiring between indoor and outdoor unitsNOTEAn outdoor unit connected with control wiring between indoor and
Contents1 Accessory Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Precautions for Saf
High Wall TypeInstallation Manual–19– Wire ConnectionREQUIREMENT• Connect the wires matching the terminal numbers.Incorrect connection causes a trou
High Wall TypeInstallation Manual–20– EN5. Clamp the wires with the cord clamp.6. Install the clamp base with a screw.7. Remove the conduit cover.8. A
High Wall TypeInstallation Manual–21– 10 Applicable ControlsA wired remote control is necessary for this function. This function cannot be operate wit
High Wall TypeInstallation Manual–22– ENProcedure 2Each time button is pushed, indoor unit numbers in the control group change cyclically. Select th
High Wall TypeInstallation Manual–23– Adjustment of air direction1. Using the remote control, change the up/down air direction by moving the horizon
High Wall TypeInstallation Manual–24– EN11 Test Run▼ In case of wired remote control Before test run• Before turning on the circuit breaker, carry ou
High Wall TypeInstallation Manual–25– ▼ In case of wireless remote control (Forced test operation is performed in a different way.)REQUIREMENT• For th
High Wall TypeInstallation Manual–26– EN12 TroubleshootingA wired remote control is necessary for this function. This function cannot be operate with
High Wall TypeInstallation Manual–27– Check codes and parts to be checkedCheck methodOn the remote control (Wired remote control, Central control re
High Wall TypeInstallation Manual–28– ENE28 E28 Detected outdoor unit number Follower outdoor unit error I/FE31 E31 IPDU communication error I/FF01 —
High Wall TypeInstallation Manual–2– EN1 Accessory Parts Accessory parts<Others>Part name Q’ty ShapeInstallation plate 1Wireless remote control
High Wall TypeInstallation Manual–29– H05 H05 — TD1 miswiring I/FH06 H06 — Low pressure protective operation I/FH07 H07 — Oil level down detective pro
High Wall TypeInstallation Manual–30– ENError detected by TCC-LINK central control deviceTCC-LINK : TOSHIBA Carrier Communication Link.P04 P0401: Comp
High Wall TypeInstallation Manual–31– WARNINGS ON REFRIGERANT LEAKAGECheck of Concentration LimitThe room in which the air conditioner is to be insta
1111053901 Confirmation of Indoor Unit SetupPrior to delivery to the customer, check the address and setup of the indoor unit, which has been installe
High Wall TypeInstallation Manual–3– 2 Precautions for SafetyInstalling, starting up, and servicing air-conditioning equipment can be hazardous due to
High Wall TypeInstallation Manual–4– EN• If refrigerant gas has leaked during the installation work, ventilate the room immediately.If the leaked refr
High Wall TypeInstallation Manual–5– 3 Selection of Installation PlaceWARNING• Install the air conditioner securely in a location where the base can s
High Wall TypeInstallation Manual–6– EN Installation diagram of Indoor and outdoor units Installation spaceThe indoor unit shall be installed so tha
High Wall TypeInstallation Manual–7– Wireless remote control• A place where there are no obstacles such as a curtain that may block the signal from
High Wall TypeInstallation Manual–8– EN Cutting a hole and mounting installation plateCutting a holeIn case of installing the refrigerant pipes from